PRODUCTS
Product Search (Keyword)
Evaluation of moisture absorption, degradation, and contamination of High Voltage Transformers.
Insulation evaluation of High Voltage Rotating Machines.
Electrical Characteristics and degradation evaluation of Lubricants.
■Single measurement enables evaluation of insulation.
No need to compare past data to analyze insulation degradation factors.
■Compact・Light weight・Battery-powered.
Easy on-site measurement with a single unit.
■The state of insulation is clearly analyzed.
No specialized expertise is required.
Frequency Domain Insulation System Diagnosis
Analyzes trends in frequency characteristics to diagnose increased moisture content and oil deterioration/contamination.
Determine moisture absorption or surface contamination trends based on capacitance and tan δ frequency characteristics.
Capable of measuring up to approx. 1000% tan δ at a test voltage of 200Vrms.
Evaluates insulation characteristics of motors containing lubricating oil.
Product name | |
---|---|
Model | DAC-FIND-1 |
Capacitance | 300pF - 2µF (4-digit display) |
tan δ | 0.01% - 999.9% (Min resolution 0.01%) |
Test Power supply | Frequency 10mHz - 100Hz Voltage 200Vrms, 20Vrms |
Power source | Battery: Nickel‐hydrogen 12V/4200mAh (Continuous operation: 4 hours) AC adaptor: Input AC100 - 240V |
Size & dimensions | W394 x D307 x H173 (mm) About 7kg |